Section has not been found.
Name of products |
Е-1,0-0,9G-3(E) |
Е-1,0-0,9М-3(E) |
Е-1,6-0,9GMN(E) |
Е-2,5-0,9GM(E) |
Е-2,5-0,9GMN(E) |
Nominal steam, t/h, at least
|
1 |
1 |
1,6 |
2,5 |
2,5 |
Operating pressure steam outlet, MPa (kgf/cm²), not more |
0,8(8,0) |
0,8(8,0) |
0,8(8,0) |
0,8(8,0) |
0,8(8,0) |
Estimated fuel |
fuel oil |
coal |
gas, fuel oil |
gas, fuel oil |
gas, fuel oil |
Steam temperature,°С |
175 |
175 |
175 |
175 |
175 |
Feedwater temperature °C |
50 |
50 |
50 |
50 |
50 |
Flue gas temperature, ° С
|
230 |
320 |
260 |
210 |
210 |
The estimated fuel consumption at rated load (natural gas, m³/h), no more |
gas-83,5
|
fuel oil-74,0 |
gas-130 fuel oil-118 |
gas-210m³ fuel oil-190 |
gas-220m³ fuel oil-186 |
Efficiency, with economiser |
91 |
|
91 |
91 |
91 |
Efficiency, without economiser |
|
87,5 |
89 |
89 |
89 |
Boiler weight, kg, not more |
4300 |
4300 |
5100 |
8100 |
6400 |
Boiler dimensions, m (L×W×H), not more |
4200 × 2350 × 2900 |
4200 × 2350 × 2900 |
4200 × 2450 × 2900 |
4440 × 3820 × 3600 |
5350 × 2450 × 3200 |